Ningbo Haimei Trading Co.,Ltd

Suspension Type Anti-pollution Insulator for High Voltage ANSI

Short Description:

The business keeps to the operation concept “scientific management, premium quality and efficiency primacy, customer supreme for Short Lead Time for Manufacture Voltage Stay Porcelain Insulat...


  • Port: Ninbo
  • Payment Terms: L/C,D/A,D/P,T/T
  • Product Detail

    Product Tags

    The business keeps to the operation concept “scientific management, premium quality and efficiency primacy, customer supreme for Short Lead Time for Manufacture Voltage Stay Porcelain Insulator, We believe you will be satisfied with our reasonable price, high quality products and fast delivery. We sincerely hope you can give us an opportunity to serve you and be your best partner!

     

    Suspension Type Anti-pollution Insulator for High Voltage ANSI图片1.png

     MAIN DIMENSIONS AND STANDARD PARTICULARS

    Cat. No. H1109

    H1110

    H1111

    H1112

    H1113

    H1114

    H1115

    H1116

    Fig

    1

    2

    3

    4

    3

    4

    5

    3

    Class ANSI

    52-1

    52-2

    52-3

    52-4

    52-5

    52-6

    52-9

    52-10

    Main Dimensions (mm)

    D

    165

    190.5

    254

    254

    254

    254

    114

    279.4

    H

    139.7

    146

    146

    146

    146

    146

    160

    165

    Creepage Distance (mm)

    178

    210

    292

    292

    279

    279

    171

    279

    Power-frequency Puncture Voltage (kV)

    80

    90

    110

    110

    110

    110

    80

    110

     

    Average flashover Voltage

    Power

    frequency

    Dry (kV)

    60

    65

    80

    80

    80

    80

    60

    80

    Wet (kV)

    30

    35

    50

    50

    50

    50

    30

    50

    Critical Impulse

    15×40 μs Wave

    Positive (kV)

    100

    115

    125

    125

    125

    125

    90

    125

    Negative (kV)

    100

    115

    130

    130

    130

    130

    100

    130

    Radio-Influence-Voltage Data

    Test Voltage to ground (kV)

    7.5

    7.5

    10

    10

    10

    10

    7.5

    10

    Maximum RIV at 1000kHz(μv)

    50

    50

    50

    50

    50

    50

    50

    50

    Electron mechanical Failing Load (KN)

    44

    67

    67

    67

    111

    111

    44

    160

    Mechanical Impact Strength (KN)

    5

    5.5

    5.5

    6

    7

    7

    5

    10

    Time Load Test Value (KN)

    27

    44

    44

    44

    67

    67

    27

    107

    We look quality as the foundation of the enterprise, adhering the management philosophy that to do less products and do not let unqualified products leave the factory.

    Packing

    P1030433

    Application Scenarios

    showimg24

    Certificate
    1

     


    We look quality as the foundation of the enterprise, adhering the management philosophy that to do less products and do not let unqualified products leave the factory.


  • Previous:
  • Next:

  • Related Products