    We take “customer-friendly, quality-oriented, integrative, innovative” as objectives. “Truth and honesty” is our administration ideal for Factory Promotional Direct Sale Low Voltage Porcelain Insulator, Winning customers’ trust is definitely the gold key to our good results! If you are fascinated in our products, make sure you sense absolutely free to go to our web site or make contact with us.

     

    Pin Type Insulators For High Voltage BS 02图片.png

     MAIN DIMENSIONS AND STANDARD PARTICULARS

    Cat. No.

    H1215

    H1216

    H1217

    H1218

    Fig

    1

    2

    3

    4

    Class BS

    Pw-11-Y

    Pw22-Y

    Pw-33-Y

    Pw-36-Y

     

     

    Main Dimensions

     

    mm

    H

    185

    255

    320

     

    h

    52.63

    52.63

    52.63

    52.63

    D

    170

    205

    240

     

    d

    76

    76

    76

     

    d1

    27.78

    27.78

    27.78

     

    R1

    16

    16

    16

     

    R2

    16

    16

    16

     

    Nominal Voltage/kV

    15

    22

    33

    33

    Creepage Distance/mm

    432

    673

    851

    900

    Power-frequency puncture voltage (kV)

    150

    200

    210

    170

    Minimum Flashover Voltage

    50% Impulse Positive

    150

    190

    210

    190

    Power-frequency

    Dry (kV)

    100

    125

    140

    130

    Wet (kV)

    65

    95

    110

    95

    Withstand Voltage

    One minute Power-frequency

    Dry (kV)

    90

    110

    125

    115

    Wet (kV)

    60

    90

    100

    85

    Impulse/kV

    140

    180

    200

    190

    Radio-Influence Voltage Data

    Test Voltage to Ground/kV

    22

    30

    44

    44

    Maximum RIV at 1000kHz/UV

    12000

    16000

    25000

    25000

    Cantilever Failing Load (KN)

    11

    11

    11

    11

    Weight (kg)

    5

    10

    13

    8.4

     