We take “customer-friendly, quality-oriented, integrative, innovative” as objectives. “Truth and honesty” is our administration ideal for Factory Promotional Direct Sale Low Voltage Porcelain Insulator, Winning customers’ trust is definitely the gold key to our good results! If you are fascinated in our products, make sure you sense absolutely free to go to our web site or make contact with us.
MAIN DIMENSIONS AND STANDARD PARTICULARS
Cat. No. |
H1201 |
H1202 |
H1203 |
H1204 |
H1205 |
Class ANSI |
55-1 |
55-2 |
55-3 |
55-4 |
55-5 |
Creepage Distance (mm) |
102 |
127 |
178 |
229 |
305 |
Dry Arcing Distance (mm) |
57 |
86 |
114 |
127 |
159 |
Cantilever Strength (KN) |
13 |
11 |
11 |
13 |
13 |
Low-frequency Wet Flashover Voltage |
35 |
45 |
56 |
65 |
80 |
Low-frequency Dry Flashover Voltage |
20 |
25 |
30 |
35 |
45 |
Critical Impulse Flashover Positive (kV) |
50 |
70 |
90 |
105 |
130 |
Critical Impulse Flashover Negative (kV) |
70 |
85 |
110 |
130 |
150 |
Power-frequency Puncture Voltage (kV) |
50 |
70 |
90 |
95 |
115 |
Test Voltage to Ground (kV) |
5 |
5 |
10 |
10 |
15 |
Maximum RIV at 1000kHz(μV) |
50 |
50 |
50 |
50 |
100 |
Net weight per each (kg) |
0.5 |
0.65 |
1 |
1.55 |
2.75 |
Number in standard package |
60 |
40 |
30 |
16 |
12 |